The installation of vortex flowmeter
1. Vortex flowmeter can only be a one-way measurement, installation, pay close attention to the direction of media flow arrows shown in the same direction with the meter.
2. Vortex flowmeter installed the best way for vertical installation, media bottom-up through the galvanometer. Be installed in vertical pipe flow meters, flow direction from the bottom up.
3. The level of installation, flow meters must be installed in the entire system of high pressure areas, and ensure that the corresponding outlet pressure; do not install the highest point in the pipeline, as is often the highest point of the accumulation of gas, pipeline of non-full, exports are not directly shorting.
4. Measuring high-temperature fluids, try to use the vertical installation mode; if it had the level of the installation, please flowmeter transmitter part of the vertically downward, or horizontal side-loaded to avoid the temperature too high; attention to air flow at the installation location or a well-ventilated.
5. Straight pipe requirements: At least 15 times before to ensure meter diameter, five times the diameter after the flow meter. Such as the elbow before meter, indent, the expansion and other sources of interference, it would take to ensure meter before the 30 - 40 times the diameter, flow meters diameter after 6 times. Flow meter should be installed at the control valve, pressure or temperature sensors upstream.
6. Note that installing pipe diameter should be slightly greater than or equal to the diameter of instruments.
7. The use of seals, attention should be slightly greater than or equal to the diameter of ring meter diameter, ring pipe center is located.