Summarizes
|
 |
|
361R Series angular travel electric actuator is based on the single-phase AC 220V power as the driving power, is a full electronic executing agency received the control signals from the computer, regulator, or operator of the 4-20mAd.c., Or 1-5Vd.c., Servo systems have built-in, no need to reprovision servo amplifier; key components of "controller" is used of the advanced hybrid integrated circuit, high reliability, moisture-proof, shock-proof; the use of the base, crank installed, the crank at 0 of the location can be arbitrary 0-360 ℃ to determine, in addition, the implementation of features overload protection, temperature protection the protection of the torque switch three protection function. Its has high precision control, is a high-reliability products.
specification
|
Type
|
Model
|
Rated output power N.m |
Times S/90° |
Max turn angle
|
|
Conventional type
|
361RSA-02 |
20 |
8.5 |
90° |
| 361RSA-05 |
50 |
17 |
| 361RSB-10 |
100 |
18 |
| 361-20 |
200 |
36 |
| 361-30 |
300 |
24 |
| 361-50 |
500 |
42 |
| 361-60 |
600 |
48 |
| 361-100 |
1000 |
30 |
| 361-150 |
1500 |
42 |
|
explosion proof type
|
361-10 |
100 |
18 |
| 361-20 |
200 |
36 |
| 361-30 |
300 |
24 |
| 361-50 |
500 |
42 |
| 361-60 |
600 |
48 |
|
Primary technology and property data
1、technology data
|
Power
|
220±10%Va.c. 50Hz |
Signal
|
4-20mAd.c. |
|
Driving engine
|
AC reversible gear reducer motor
|
Control limit switch |
open side or close side
|
|
control signal
|
4-20mAd.c. 1-5Vd.c. |
Protect rate
|
IP55 |
|
turn angle test
|
exact conductive plastic regulation resistance
|
Installation
|
Anyway
|
|
Power consumption
|
A |
50VA |
wiring access
|
2-PF1/2〔A.B.C common type〕
2-PF3/4〔common type and explosion proof type〕
|
| B |
150VA |
Line
|
Signal line screen and separate with the power line
|
| C |
220VA |
Explosion sign
|
Exd‖BT4 |
| D |
350VA |
Allow temp℃ |
The common one don’t has space heater
|
-10--+60 |
|
With space heater
|
-35--+60 |
|
resolution
|
<0.4% |
Gas economic |
No aggressive gas
|
|
Adjusting range
|
Zero point |
±25% |
Allow shock
|
Below1.5G |
|
Turn angle
|
20%--100% |
RH
|
Common type under 95%,explosion proof type 45%--85% |
2、performance index
|
project
|
target value
|
|
Basic error %
|
± .0 |
|
Return different %
|
1.0 |
|
Dead area %
|
0.8-1.0 can be adjust to0.4 |
|
?resolution %
|
<0.4 |
|
Adjusting range
|
Zero point±25% travel20%-100% |
3、actuator inside connection drawing(the same with 3610L direct travel electronic electric actuator)
Outlook size
1、angle travel electronic electric actuator outlook size
|
model
|
D1 |
D2 |
H1 |
H2 |
h1 |
h2 |
d1 |
d2 |
d3〔18〕 |
□J |
K |
n |
M |
W |
Y |
R |
WeightKg
|
| 361RSA |
225 |
260 |
185 |
120 |
65 |
30 |
90 |
70 |
55 |
□16 |
12 |
4 |
M8 |
56 |
200 |
φ160 |
7 |
| 361RSB |
255 |
290 |
225 |
155 |
65 |
30 |
90 |
70 |
55 |
□21 |
12 |
8 |
M8 |
68 |
225 |
φ320 |
12 |
| 361RXB |
270 |
310 |
275 |
175 |
65 |
30 |
90 |
70 |
55 |
□21 |
12 |
8 |
M8 |
68 |
265 |
φ320 |
21 |
| 361RSC |
335 |
380 |
265 |
165 |
85 |
35 |
125 |
102 |
70 |
□32 |
18 |
4 |
M10 |
80 |
260 |
φ320 |
42 |
| 361RSD |
470 |
520 |
390 |
120 |
85 |
50 |
150 |
125 |
85 |
□41 |
24 |
4 |
M12 |
65 |
265 |
φ400 |
150 |
note:H2 in the table is the need size when unload the cleading, R is the needed size of the level operated,it must be considered when design install 。
2、RSA、RSB-type with seat and crank size
|
model
|
h1 |
h2 |
h3 |
h4 |
L1 |
L2 |
L3 |
L4 |
L5 |
L6 |
L7 |
L8 |
R |
R1 |
R2 |
H2 |
Y |
Weight Kg |
| 361RSA |
56 |
120 |
15 |
289 |
100 |
220 |
250 |
200 |
50 |
21 |
100 |
130 |
φ130 |
φ16 |
4-φ13 |
135 |
200 |
14 |
| 361RSB |
68 |
120 |
15 |
316 |
120 |
220 |
250 |
240 |
50 |
21 |
100 |
130 |
φ320 |
φ16 |
4-φ13 |
155 |
225 |
21 |
te:H2 in the table is the need size when unload the cleading, R is the needed size of the level operated,it must be considered when design install 。
3、RSC-type with seat and crank size
|
Model
|
h1 |
h2 |
h3 |
h4 |
L |
L1 |
L2 |
L3 |
L4 |
L5 |
L6 |
L7 |
L8 |
L9 |
L10 |
R |
R1 |
R2 |
H2 |
WeightKg |
| 361RSC |
80 |
190 |
20 |
358 |
260 |
150 |
320 |
380 |
395 |
55 |
23 |
180 |
220 |
335 |
415 |
φ320 |
φ18 |
4-φ14 |
165 |
64 |
note:H2 in the table is the need size when unload the cleading, R is the needed size of the level operated,it must be considered when design install 。
4、RSD-type with seat and crank size
|
Model
|
h1 |
h2 |
h3 |
h4 |
L |
L1 |
L2 |
L3 |
L4 |
L5 |
L6 |
L7 |
L8 |
R |
R1 |
R2 |
H2 |
D |
Weight Kg |
| 361RSD |
65 |
305 |
45 |
310 |
365 |
170 |
390 |
464 |
390 |
85 |
25 |
180 |
121 |
φ400 |
φ18 |
4-φ14 |
285 |
470 |
165 |
note:H2 in the table is the need size when unload the cleading, R is the needed size of the level operated,it must be considered when design install 。
5、Bracket parts list
The size is just for reference,When you choose a right valve for matching equipment, you should’ better culculate the valve’s torque according to the allowed pressure deviation;then you can make sure that the actuator’s output force is stronger than the force to turn on or turn off the valve. The companion flanges dimensions in this form is just for your reference.
|
model
|
Diameter of the
?butterfly valve
|
Brocket code
|
H |
D |
B1 |
B2 |
d1 |
t |
H1 |
H2 |
D |
□J |
| 361RSA-05 |
50-100 |
RA1 |
62 |
φ14 |
75 |
34 |
φ12 |
4 |
43 |
20 |
φ32 |
16 |
|
361RSA-05
361RSB-10、20
|
125-200 |
RB2 |
62 |
φ18 |
110 |
34 |
φ12 |
6 |
50 |
25 |
φ32 |
16 |
| 63 |
35 |
φ41 |
21 |
| 361RSB-10、20 |
250-350 |
RB3 |
70 |
φ24 |
130 |
40 |
φ14 |
6 |
63 |
35 |
φ43 |
21 |
| 361RSC-30 |
250-350 |
RC3 |
70 |
φ24 |
130 |
40 |
φ14 |
6 |
72 |
35 |
φ60 |
32 |
| 361RSC-30、50、60 |
400-500 |
RC4 |
78 |
φ30 |
150 |
60 |
φ18 |
8 |
78 |
40 |
φ78 |
32 |
Notice when make the order
You must give the detail data when order:
|
1、Basic model of the product
|
2、Whether take overpower protect or not
|
3、Brocket code
|
|
4、Whether take ?moment switch or not
|
5、Whether take space heater or not
|
6、Whether take outside limit chest or not〔explosion proof type〕
|